
Firms can save one million kilowatt hours a year
byimplementing 11 best practices in their
datacentres, according to analyst
Gartner.
Gartner says that in a
conventional datacentre, 35% to 50% of the electricity consumed
is for cooling. The figure is 15% in best-practice "green"
datacentres.
"Virtually all datacentres waste enormous amounts of electricity
using inefficient cooling designs and systems," said Paul McGuckin,
an analyst at Gartner. "Even in a small datacentre, this wasted
electricity amounts to more than one million kilowatt hours
annually, that could be saved with the implementation of some best
practices."
The overriding reason for the waste in conventional datacentre
cooling is the unconstrained mixing of cold supply air with hot
exhaust air, said Gartner.
"This mixing increases the load on the cooling system and energy
used to provide that cooling, and reduces the efficiency of the
cooling system by reducing the delta-T (the difference between the
hot return temperatures and the cold supply temperature). A high
delta-T is a principle in cooling," said Paul McGuckin.
Gartner's 11 best practices:
- Plug holes in the raised floor
Most raised-floor environments have cable holes, conduit holes and
other breaches that allow cold air to escape and mix with hot air.
This single low-tech retrofit can save as much as 10% of the energy
used for datacentre cooling. - Install blanking panels
Any unused position in a rack needs to be covered with a blanking
panel to manage airflow in a rack by preventing the hot air
entering the cold-air intake of other equipment in the same rack.
When the panels are used effectively, supply air temperatures are
lowered by as much as 22°F (5.6°C), greatly reducing the
electricity consumed by fans in the IT equipment, and alleviating
hot spots in the datacentre. - Co-ordinate CRAC units
Older computer room air-conditioning units (CRACs) operate
independently in cooling and dehumidifying the air. These units
should be tied together with newer technologies so efforts are
co-ordinated. Alternatively, humidification responsibilities can be
removed from them altogether and place with a newer piece of
technology. - Improve underfloor airflow
Older datacentres typically have constrained space underneath the
raised floor that is not only used for the distribution of cold
air, but also has served as a place for data cables and power
cables. Many old datacentres have accumulated such a tangle of
these cables that airflow is restricted, so the underfloor should
be cleaned out to improve airflow. - Implement hot aisles and cold aisles
In traditional datacentres, racks were set up in what is sometimes
referred to as a "classroom style," where all the intakes face in a
single direction. This arrangement causes the hot air exhausted
from one row to mix with the cold air being drawn into the adjacent
row, thereby increasing the cold-air-supply temperature in uneven
and sometimes unpredictable ways. Newer rack layout practices
instituted in the past 10 years demonstrate that organising rows
into hot aisles and cold aisles is better at controlling the flow
of air in the datacentre. - Install sensors
A small number of individual sensors can be placed in areas where
temperature problems are suspected. Simple sensors store
temperature data that can be transferred into a spreadsheet, where
it can be further analysed. This can provide insight into possible
datacentre temperature problems, as well as a method for analysing
the results of improvements made to datacentre cooling. - Implement cold-aisle or hot-aisle
containment
Once a datacentre has been organised around hot aisles and cold
aisles, dramatically improved separation of cold air supply and hot
exhaust air through containment becomes an option. For most users,
hot-aisle containment or cold-aisle containment will have the
single largest payback of any of these energy efficiency best
practices. - Raise the temperature in the datacentre
Many datacentres are run colder than an efficient standard. The
American Society of Heating, Refrigerating, and Air-Conditioning
Engineers (ASHRAE) has
increased
the top end of allowable supply-side air temperatures from 77°F
(25°C) to 80°F (26.7°C). Not all datacentres should be run at the
top end of this temperature range, but a step-by-step increase,
even to the 75°F (23.9°C) to 76°F (24.4°C) range, would have a
beneficial effect on datacentre electrical use. - Install variable speed fans and pumps
Traditional CRAC units contain fans that run at a single speed.
Emerging best practice suggests variable speed fans be used
whenever possible. A reduction of 10% in fan speed yields a
reduction in the fan's electrical use of around 27%. A 20% speed
reduction yields electrical savings of around 49%. - Exploit "free cooling"
"Free cooling" is the general name given to any technique that
cools air without the use of chillers or refrigeration units. The
two most common forms of free cooling are air-side economisation
and water-side economisation. The amount of free cooling available
depends on the local climate, and ranges from approximately 100
hours per year to more than 8,000 hours per year. - Design datacentres using modular
cooling
Traditional raised-floor-perimeter air
distribution systems have long been the method used to cool
datacentres. However, mounting evidence strongly points to the use
of modular cooling (in-row or in-rack) as more
energy-efficient.
"Although most users will not be able to immediately implement
all 11 best practices, all users will find at least three or four
that can be immediately implemented in their current datacentres,"
said McGuckin.
"Savings in electrical costs of 10 to 30% are achievable through
these most-available techniques. Users committed to aggressively
implementing all 11 best practices can achieve an annual savings of
1 million kilowatt hours in all but the smallest tier of
datacentres," he said.
Gartner will be discussing power and cooling strategies at the
Gartner Data Center Conference on 2-5 December in Las Vegas.